Fisher Tank Blanketing & Vapor Recovery Regulators

Tank Blanketing & Vapor Recovery Regulators

Pad-Depad

Tank Blanketing (Pad)


Vapor Recovery

 

Fisher-ACE97 Series Pad-Depad

The 97 Series simplifies the process of make-up and vent by combining both functions in one unit. This series is a unique, patented valve which incorporates all the standard features in our Type ACE95 Series valves. 

We Have a Better Way: Gas In - Gas Out "One Unit"
The unit consists of a single actuator that controls the entire operation. Pad (make-up) and depad (venting) are controlled by the actuator.

The diaphragm in the actuator has a long stroke. It is biased by a single range spring set that controls both pad and depad setpoints independently.These setpoints are both adjustable.

At the bottom (lower pressure) of its stroke, the diaphragm acutates the pad valve to control the flow of inert gas to the tank vapor space.

Pump out of tank contents or a drop in vapor space temperature will cause the tank pressure to drop below pad setpoint. The diaphragm will move down and actuate the pad valve. Inert gas will be throttled into the tank.

As the pressure rises to pad setpoint, the diaphragm also rises. This deactuates the pad valve and flow of inert gas ceases. Pump in or a rise in vapor space temperature will cause the tank pressure to rise. The diaphragm will move upward and when the pressure reaches the depad setpoint, it will actuate the depad pilot valve. This throttles the depad main valve, venting the tank vapor space and controlling the pressure.

Both the pad valve and depad valve are plilot controlled (except for the 1/2" body pad valve). Shut-off is tight and positive. The inert gas supply is used to operate both valves and provides a positive force against the valve seats to ensure tight shut-off. The valves are soft seated and bubble tight up to their setpoints.

Typically, the pad valve operates within a 0.5 inch water column band below its setpoint.

Features

  • Stainless Steel - bodies and bonnets of 316 or CF8M/CFM
  • Pad Cv 0.2 to 60, Depad Cv 3 to 280 for all applicationrequirements
  • Fully balanced pilot valves for accuracy and reduction offriction/hysteresis
  • Normally open Depad main valve vents tank in case of gasfailure
  • Normally closed Pad main valve prevents backflow in case of gasfailure
  • High Sensitivity provided by a single, large actuator withrolling diaphragm
  • Pad and Depad settings controlled by a single actuator
  • Set points 0.5 in. wc (1.2 mbar) to 4.2 psi (0.29 bar)
  • Inlet pressures to 200 psi (13.8 bar)
  • Diagnostic port for servicing


Connections

  • Tank and vapor connections are available to meet most customer requirements.
  • Single Array Manifold (S.A.M.) units provide a single tank and sensing connection. Required for tanks having a single nozzle available


Materials

  • These units are stainless steel construction. Seals and diaphragms are available in a variety of materials to satisfy the application


Accessories

  • Gauges, purge meters, pressure switches and check valves are available on request.

Back to top

66 Series Pressure Reducing Regulators




The Type 66 self-operated regulator maintains a reduced outlet pressure while satisfying the downstream flow demands.  The Type 66Z and 66ZZ self-operated regulators also control a reduced outlet pressure; however, both have springs sensitive to negative pressures and can be used for vacuum regulation.  Each regulator type has a balancing diaphragm which increases accurate and sensitive response to pressure changes by reducing the unbalanced forces acting on the valve plug. 

 

 

Features

  • Sensitive Response to Pressure Changes
  • Seat Protection without Sacrifice in Shutoff Capability
  • Accuracy
  • Application Flexibility
  • Dirty Service and Sour Gas Capability


Body Sizes and End Connection Styles

  • Cast Iron
    • 2, 3 or 4-inch (DN 50, 80 or 100) body size NPT or 125 FF
  • Steel and Stainless Steel
    • 2-inch (DN 50) body size NPT, 150 FF, 150 RF, or 300 RF
    • 3-inch (DN 80) body size 150 RF or 300 RF
    • 4-inch (DN 100) body size 150 RF


Maximum Inlet Pressures

  • Emergency Inlet Pressure: 25 psig (1,7 bar)
  • Maximum Pressure to Avoid Internal Parts Damage: 10 psig (0,69 bar)


Maximum Outlet (Casing) Pressure

  • 8 psig (0,55 bar)


Outlet Pressure Ranges

  • 4-inches w.c. to 5 psig (10 to 0,34 bar) in 11 ranges


Temperature Capabilites

  • -40º to 180°F (-40 to 82°C)


Pressure Registration

  • Cast Iron Body: Internal (standard) or External
  • Steel Body: External


Approximate Shipping Weights

  • 2-inch (DN 50)
    • Screwed Ends, Pounds (kg):  50 (23)
    • Flanged Ends, Pounds (kg): 55 (25)
  • 3-inch (DN 80)
    • Flanged Ends, Pounds (kg): 100 (45)
  • 4-inch (DN 100)
    • Flanged Ends, Pounds (kg):  155 (70)

Back to top

Type 1190 Tank Blanketing Valve




The Type 1190 low pressure gas blanketing valve is a pilot-operated, pressure reducing valve with a supply pressure regulator. This valve is used for extremely accurate pressure control on very low pressure gas blanketing systems. The Type 1190 helps to control emissions and provides protection against any contamination from atmospheric conditions by providing a flushing action.
The Type 1190 gas blanketing valve maintains a positive vessel pressure thereby reducing the possibility of vessel wall collapse during pumpout operations.

 

Features

  • Quick-Change Trim Package
  • Easy In-Line Maintenance
  • Factory-Piped Pilot Supply
  • 1/4-Inch w.c. (0,6 mbar) Setpoint
  • Whisper Trim" Cage


Body Size and End Connection Styles

  • Cast Iron
    • 1-inch (DN 25) body size NPT screwed, 125 FF or 250B RF end connections
    • 2-inch (DN 25)
    • 3-inch (DN 80)
    • 4-inch (DN 100)
    • 6-inch (DN 150) body size 125 FF or 250B RF end connections
  • WCB Steel or CF8M Stainless Steel
    • 1-inch (DN 25) body size NPT screwed, 150 RF, 300 RF, or PN 16/25/40 end connections
    • 2-inch (DN 25)
    • 3-inch (DN 80)
    • 4-inch (DN 100)
    • 6-inch (DN 150) body size, 150 RF, 300 RF, or PN 16/25/40 end connections


Maximum Inlet Pressure

  • 200 psig (13,8 bar); or 300 psig (20,7 bar) with a steel or stainless steel body Type 95H supply regulator


Maximum Outlet (Casing) Pressure

  • 75 psig (5,2 bar)


Outlet Pressure Ranges

  • 1/4-inch w.c. to 7 psig (0,6 mbar to 0,48 bar) in seven ranges


Pressure Registration

  • External


Temperature Capabilites

  • Nitrile: -20 to 180°F (-29 to 82°C)
  • Fluoroelastomer (FKM): 40 to 300°F (4 to 149°C)
  • Ethylenepropylene (EPDM): 20 to 300°F (-29 to 149°C)
  • Perfluoroelastomer (FFKM): -20 to 300°F (-29 to 149°C)


Approximate Weight

  • 1-inch (DN 25):  85 pounds (39 kg)
  • 2-inch (DN 50):  100 pounds (45 kg)
  • 3-inch (DN 80):  145 pounds (66 kg)
  • 4-inch (DN 100):  195 pounds (88 kg)
  • 6-inch (DN 150):  380 pounds (172 kg)
  • 8x6-inch (DN 200):  740 pounds (336 kg)

Back to top

Type ACE95 Series Tank Blanketing Valve

Tank blanketing is the process of using a gas, such as nitrogen, to maintain a slightly positive pressure in an enclosed storage tank. Tank blanketing prevents a stored product from vaporizing into the atmosphere, reduces product combustibility, and prevents oxidation or contamination of the product by reducing its exposure to air. Tank blanketing is utilized with various products, including: adhesives, pharmaceuticals, pesticides, fertilizers, fuels, inks, photographic chemicals, and food additives.
Types ACE95 and ACE95Sr valves are self-contained, fully balanced, pilot-operated, and are used for accurate pressure control on tank blanketing systems. These valves help control emissions and provide protection against atmospheric contamination. Types ACE95 and ACE95Sr valves maintain a positive tank pressure which reduces the possibility of tank wall collapse during pump out operations, prevents stored product from vaporizing to atmosphere.


Features

  • Fully Balanced Pilot Design Reduces Inlet Pressure Sensitivity
  • Frictionless Pilot Valve
  • Bubble Tight Shut-Off
  • Pilot Controlled
  • Angled or In-Line Body Option
  • Self-Contained
  • Highly Sensitive
  • Diagnostics Available
  • Vacuum Settings Available
  • Stainless Steel Construction Available


End Connection Styles

  • Type ACE95
    • Angled Body*
      • 3/4-inch (DN 20) NPT
      • 1-inch (DN 25) NPT, CL150RF, CL300RF, PN 16/25/40RF, Sanitary Flange
    • In-Line Body
      • 3/4-inch (DN 20) NPT
      • 1-inch (DN 25) NPT, CL150RF, CL300RF, PN 16/25/40RF, Sanitary Flange
      • 1 x 2-inch (DN 25 x 50) CL150RF, PN 16/25/40RF
  • Type ACE95Sr
    • Angled Body*
      • 2-inch (DN 50) NPT, CL150RF, CL300RF


*Various Single Array Manifold (SAM) tank connections are also available.  Contact your Control Southern Sales Representative for more information.

Maximum Inlet Pressure

  • 200 psig (13,8 bar)


Outlet Pressure Ranges

  • -5-inch w.c. to 1.5 psig (-12,4 to 103 mbar)


Pressure Registration

  • External


Temperature Capabilites

  • Nitrile (NBR): -20° to 180°F (-29° to 82°C)
  • Fluoroelastomer (FKM): 0° to 212°F (-18° to 100°C)
  • Ethylenepropylene (EPDM - FDA): -20° to 212°F (-29° to 100°C)


Approximate Weight

  • 40 lbs (18,1 kg)

Back to top

Type ACE95jr Tank Blanketing Valve

The Type ACE95jr is a direct-operated valve used for accurate pressure control on low-pressure blanketing systems. The unit is stainless steel, and actuated by a very large diaphragm actuator. Blanketing setpoint is controlled by a single adjusting screw.
The oversized actuator offers high sensitivity to changes in tank pressure, increasing accuracy. A rolling diaphragm is utilized to maintain a fully balanced main valve, insuring extremely accurate operation under all conditions. Lockup is typically less than 0.3 inches w.c. (1,2 mbar). The main valve stroke is minimal to further insure accuracy and fast response.

 

Features

  • Stainless Steel Construction
  • Fully Balanced Main Valve
  • Rolling Diaphragm
  • High Sensitivity
  • Extremely Accurate Control
  • Chemically Compatible Elastomers
  • Optional Single Tank Connection
  • No Minimum Inlet Pressure
  • Designed For Low Flow Service


End Connection Styles

  • 1/2, 1/2 x 1 or 1-inch (DN 15, 15 x 25 or 25) NPT
  • Class 150 RF flanged or PN10/16 flanged
  • 1-inch (DN 15) is also available with sanitary flanges

Note: Class 150 RF and PN 10/16 flanges are nipple mounted.

Maximum Inlet Pressure

  • 200 psig (13,8 bar)


Outlet Pressure Ranges

  • -5 inch w.c. to 5 psig (-12 mbar to 0,35 bar) in six ranges.


Pressure Registration

  • External


Temperature Capabilites

  • Buna-N® (Nitrile-NBR): -20° to 180°F (-29° to 82°C)
  • Viton® (Fluoroelastomer - FKM): 40° to 300°F (4° to 149°C)
  • FDA/EPDM (Ethylenepropylene): -20° to 300°F (-29° to 149°C)
  • Chemraz® (Perfuoroelastomer - FFKM): -20° to 300°F (-29° to 149°C)
  • Teflon® (PTFE): -20° to 300°F (-29° to 149°C)

Back to top

Type ACE95SR Series Tank Blanketing Valve


Tank blanketing is the process of using a gas, such as nitrogen, to maintain a slightly positive pressure in an enclosed storage tank. Tank blanketing prevents a stored product from vaporizing into the atmosphere, reduces product combustibility, and prevents oxidation or contamination of the product by reducing its exposure to air. Tank blanketing is utilized with various products, including: adhesives, pharmaceuticals, pesticides, fertilizers, fuels, inks, photographic chemicals, and food additives.
Types ACE95 and ACE95Sr valves are self-contained, fully balanced, pilot-operated, and are used for accurate pressure control on tank blanketing systems. These valves help control emissions and provide protection against atmospheric contamination. Types ACE95 and ACE95Sr valves maintain a positive tank pressure which reduces the possibility of tank wall collapse during pump out operations, prevents stored product from vaporizing to atmosphere.


Features

  • Fully Balanced Pilot Design Reduces Inlet Pressure Sensitivity
  • Frictionless Pilot Valve
  • Bubble Tight Shut-Off
  • Pilot Controlled
  • Angled or In-Line Body Option
  • Self-Contained
  • Highly Sensitive
  • Diagnostics Available
  • Vacuum Settings Available
  • Stainless Steel Construction Available


Size and End Connection Style

  • Angled Body*
    • 2-inch (DN 50) NPT, CL150RF, CL300RF

*Various Single Array Manifold (SAM) tank connections are also available.  Contact your local Sales Office for more information.

Pressure Registration

  • External


Maximum Inlet Pressure

  • 200 psig (13,8 bar)


Outlet Pressure Ranges

  • -5 inches w.c. to 1.5 psig (-12 mbar to 103 mbar) in six ranges


Temperature Capabilites

  • Nitrile (NBR): -20° to 180°F (-29° to 82°C)
  • Fluoroelastomer: 0° to 212°F (-18° to 100°C)
  • Ethylenepropylene (EPDM - FDA): -20° to 212°F (-29° to 100°C)
  • FFKM: -20° to 212°F (-29° to 100°C)


Approximate Weight

  • With all accessories:  60 lbs (27,2 kg)

Back to top

Y690A Series Tank Blanketing Valve

The Y690A Series Gas Blanketing Regulator System reduces a high-pressure gas, such as nitrogen, to maintain a protective environment above any liquid stored in a tank or vessel. The regulator system replaces the volume of vapors with a volume of blanketing gas to prevent the internal vessel pressure from decreasing, when liquid is being pumped out or when the vessel is suddenly cooled, causing vapors to contract. In both cases a slight positive vessel pressure prevents outside, air, moisture and other contaminants from entering the vessel. The Type Y690A is a direct-operated regulator used for accurate pressure control on very low pressure blanketing systems. Downstream pressure is sensed through a pitot tube installed in the lower casing of the regulator, thus no external control line is required. The Type Y690AM uses a control line to more accurately control the pressure if the regulator is mounted away from the tank.

Features

  • Easy Conversion Between Constructions
  • Sour Gas Service Capability
  • Inlet Pressure Equals Outlet Pressure
  • Corrosion Resistance
  • Multiple Applications


Body Sizes

  • 3/4 or 1-inch (DN 20 or 25)


Maximum Allowable Inlet Pressure

  • 150 psig (10,3 bar)


Maximum Outlet Pressure (Casing)

  • 150 psig (10,3 bar)


Maximum Emergency Outlet Pressure to Avoid Internal Parts Damage

  • 150 psig (10,3 bar)


Material Temperature Capabilities

  • Nitrile (NBR): -20 to 180º F (-29 to 82ºC)
  • Fluoroelastomer (FKM): 40 to 300ºF (4 to 149ºC)
  • Ethylenepropylene (EPDM): -20 to 300ºF (-29 to 149ºC)
  • Perfluoroelastomer(FFKM): -20 to 300ºF (-29 to 149C)


Pressure Setting Adjustment

  • Adjusting

Spring Case Connection

  • 1/4-inch NPT


Diaphragm Case Connection

  • 1/2-inch NPT

Back to top

Type Y692 Tank Blanketing Valve

The Accu-Pressure Type Y692 gas blanketing regulator is a pressure reducing self-operated regulator with internal registration requiring no downstream control line. It is used for accurate pressure control on very low pressure blanketing systems. Blanketing with low pressure gas helps prevent corrosion, helps control emissions from the blanketed product and helps protect against any contamination to the blanketed product by atmospheric conditions.
The regulator will maintain a positive vessel pressure reducing the possibility of vessel wall collapse. The Type Y692 is available in 1-1/2 or 2-inch (DN 40 or 50) body sizes.

Features

  • In-Line Inspection and Maintenance
  • Accuracy of Control
  • Speed of Response
  • Ease of Installation


Body Sizes and End Connection Styles

  • Cast Iron
    • 1-1/2-inch (DN 40) body size NPT end connection
    • 2-inch (DN 50) body size NPT or 125 FF end connections
  • Steel or Stainless Steel
    • 1-1/2 or 2-inch (DN 40 or 50) body size NPT, SWE, 150 RF, 300 RF, or PN 16/25/40 end connections
  • Hastelloy C
    • 1-1/2 or 2-inch (DN 40 or 50) body size 150 RF end connections


Temperature Capabilites

  • Nitrile: -20 to 180°F (-29 to 82°C)
  • Fluoroelastomer (FKM): 40 to 300°F (4 to 149°C)
  • Perfluoroelastomer (FFKM): -20 to 300°F (-29 to 149°C)


Maximum Inlet Pressure

  • 150 psig (10,3 bar)


Maximum Outlet (Casing) Pressures

  • Operating: 3 psig (0,21 bar) above outlet pressure setting
  • Emergency: 15 psig (1,0 bar)


Outlet Pressure Ranges

  • 1-inch w.c. to 10 psig (2,5 mbar to 0,69 bar) in seven ranges


Pressure Registration

  • Internal (standard) or External

Back to top

Type Y693 Tank Blanketing Valve




The Type Y693 is a direct-operated regulator used for accurate pressure control on low pressure blanketing systems. This unit features a balanced valve plug which allows for accuracy classes equivalent to a pilot-operated regulator.

 

 

Features

  • In-Line Inspection and Maintenance
  • Accuracy of Control
  • Insensitive to Inlet Pressure Fluctuations
  • Fast Speed of Response
  • High Flow Capacities
  • Balanced Trim Design
  • 1/2-Inch w.c. (1,2 mbar) Setpoint

Body Sizes and End Connection Styles

  • Cast Iron
    • 1-1/2 inch (DN 40) body size NPT end connection
    • 2-inch (DN 50) body size NPT, 125 FF, or 250 RF end connections
  • Steel or Stainless Steel
    • 1-1/2 or 2-inch (DN 40 or 50) body size NPT, SWE, 150 RF, 300 RF, or PN 16/25/40 end connections


Flow Coefficients

  • Wide-Open Cg: 185
  • Wide-Open Cv: 5.6
  • C1: 33


Temperature Capabilites

  • Nitrile: -20 to 180°F (-29 to 82°C)
  • Fluoroelastomer (FKM): 40 to 300°F (4 to 149°C)
  • Perfluoroelastomer (FFKM): -20 to 300°F (-29 to 149°C)


Maximum Inlet Pressure

  • 150 psig (10,3 bar)


Maximum Outlet Pressures

  • Operating: 2 psig (0,14 bar) above outlet pressure setting
  • Emergency Casing: 15 psig (1,0 bar)


Outlet Pressure Ranges

  • 1/2-inch w.c. to 10 psig (1,2 mbar to 0,69 bar) in 10 ranges


Pressure Registration

  • External

Back to top

66R Series Vapor Recovery Valves




The 66R vapor recovery regulators respond to changes in blanket gas pressure and throttle open or closed to control the flow of the blanket gas out of the vessel. A vacuum source on the outlet of the regulator can be used to increase flow capacity of low-pressure blanket gas out of the vessel into a vapor disposal or reclamation system. The Type 66R uses a pilot to decrease buildup and provide even higher accuracy

 

Features

  • Low Setpoints
  • Highly Accurate
  • Simple Design
  • High Flow Rates


Body Sizes and End Connection Styles

  • Cast Iron
    • 2-inch (DN 50) body size NPT screwed or 125 FF end connections
    • 3-inch (DN 80) or 4-inch (DN 100) body size 125 FF end connections
  • Steel or Stainless Steel
    • 2-inch (DN 50) body size NPT screwed or 150 RF end connections
    • 3-inch (DN 80) or 4-inch (DN 100) body size 150 RF end connections


Pressure Registration

  • Type 66R: Internal (Standard) or External
  • Type 66RR: External


Maximum Inlet Pressure
Type 66R:
8 psig (0,55 mbar)
Type 66RR: 10 psig (0,69 mbar)

Set Pressure Ranges

  • Type 66R: 2-inches w.c. to 3 psig (5 to 207 mbar) in six ranges
  • Type 66RR: 3-inches w.c. to 3.25 psig (7 to 224 mbar) in seven ranges


Temperature Capabilites

  • Nitrile: -20 to 180°F ( -29 to 82°C)
  • Fluoroelastomer (FKM): 40 to 300°F (4 to 149°C)

Back to top

Type 1290 Vapor Recovery Valve





The 1290 vapor recovery regulator is a self contained, pilot operated regulator system used for vapor recovery of blanketing gas. When blanketing gas pressure inside the vessel rises due to thermal heating or pumping-in of product, the Type 1290 regulator senses an increase in vessel pressure and vents excessive internal tank pressure to a vapor recovery storage tank.

 

Features

  • Quick-Change Trim Package
  • Easy In-Line Maintenance
  • High Accuracy
  • Proven Technology
  • Setpoints as low as 1/2-inch w.c. (1,2 mbar)
  • Whisper Trim" Cage


Body Size and End Connection Styles

  • Cast Iron
    • 1-inch (DN 25), or 2-inch (DN 50) body size NPT screwed, 125 FF, or 250B RF end connections
    • 2-inch (DN 25), 3-inch (DN 80), 4-inch (DN 100), or 6-inch (DN 150) body size 125 FF or 250B RF end connections
  • WCB Steel or CF8M Stainless Steel
    • 1-inch (DN 25), or 2-inch (DN 50) body size NPT screwed, 150 RF, 300 RF, or PN 16/25/40 end connections
    • 2-inch (DN 25), 3-inch (DN 80), 4-inch (DN 100), or 6-inch (DN 150) body size 150 RF, 300 RF, or PN 16/25/40 end connections


Pressure Registration

  • External


Maximum Inlet Pressure

  • 75 psig (5,2 bar)


Maximum Outlet (Casing) Pressure

  • 75 psig (5,2 bar)


Outlet Pressure Ranges

  • 1/2-inch w.c. to 7-psig (1,2 mbar to 0,48 bar) in eight ranges


Temperature Capabilites

  • Nitrile: -20 to 150°F (-29 to 66°C)
  • Fluoroelastomer (FKM): 40 to 300°F (4 to 149°C)
  • Ethylenepropylene (EPDM): -20 to 300°F (-29 to 149°C)
  • Perfluoroelastomer (FFKM): -20 to 300°F (-29 to 149°C)


Approximate Weights

  • 1-inch (DN 25): 85 pounds (39 kg)
  • 2-inch (DN 50): 100 pounds (45 kg)
  • 3-inch (DN 80): 145 pounds (66 kg)
  • 4-inch (DN 100): 195 pounds (88 kg)
  • 6-inch (DN 150): 380 pounds (172 kg)
  • 8 x 6-inch (DN 200): 740 pounds (336 kg)

Back to top


Type Y695A Vapor Recovery Valve


The Y695A backpressure/relief valves are direct-operated and are used to maintain a constant inlet pressure or vessel pressure with the outlet flowing to atmosphere or to a system whose pressure is lower than the inlet.
The Type Y695AM has a blocked throat and O-ring stem seat to allow for external pressure registration.  The lower diaphragm case is tapped 1/2-inch NPT for control line connection.


Features

  • Ease of inspection and maintenance
  • Precise control
  • Rugged construction
  • Simplicity
  • NACE construction available


Body Sizes

  • 3/4 or 1-inch (DN 20 or 25)


Maximum Inlet Pressure

  • 150 psig (10,3 bar)


Relief Set Pressure Range

  • 2-inches w.c. to 7 psig (5 mbar to 0,48 bar) in six ranges


Pressure Registration

  • Type Y695A: Internal
  • Type Y695AM: External


Temperature Capabilities

  • Nitrile (NBR): -20 to 180°F (-29 to 82°C)
  • Fluoroelastomer (FKM): 40 to 300°F (4 10 149°C)
  • Perfluoroelastomer (FFKM): -20 to 300°F (-29 to 149°C)
  • Ethylenepropylene (EPDM): -20 to 275°F (-29 to 135°C)

Back to top


Type Y696 Vapor Recovery Valve

 

The Type Y696 is a direct-operated backpressure/relief valve with internal registration requiring no downstream control line. The Type Y696 is used to sense an increase in pressure and vent excessive pressure to atmosphere.


Features

  • Ease of inspection and maintanence
  • Precise control
  • Rugged construction
  • Simplicity
  • Low setpoint


Body Sizes and End Connection Styles

  • Cast Iron
    • 1-1/2 or 2-inch (DN 40 or 50) body size NPT end connection
  • Stainless Steel
    • 1-1/2 or 2-inch (DN 40 or 50) body size NPT, 150 RF, 300 RF, or PN 16/25/40 end connections
  • Hastelloy C
    • 1-1/2 or 2-inch (DN 40 or 0) body size 150 RF end connection


Flow Coefficients

  • Wide-Open Cg: 515
  • Wide-Open Cv: 14.7
  • C1: 35


Temperature Capabilites

  • Nitrile: -20 to 180°F (-29 to 82°C)
  • Fluoroelastomer (FKM): 40 to 300°F (4 to 149°C)
  • Perfluoroelastomer (FFKM): -20 to 300°F (-29 to 149°C)
  • Ethylenepropylene: -20 to 275°F (-29 to 135°C)


Maximum Inlet Pressure
15 psig (1,0 bar)

Relief Set Pressure Ranges

  • 2-inches w.c. to 7 psig (5 mbar to 0,48 bar) in six ranges
    Pressure Registration - Internal

Back to top

 
Copyright © ICOM 2010. All rights reserved.