Fisher Natural Gas - City Gate / District Station Regulators

Natural Gas Regulators

City Gate / District Station Regulators

 

Type 99 Pressure Reducing Regulator

The Type 99 regulator typically provides fuel gas to boilers, furnaces, ovens, mixers, and large commercial or institutional installations.

The key to the operation of a Type 99 regulator is the yoked double-diaphragm pilot. Fast response and accuracy are made possible by the amplifying effect of the pressure-balanced pilot and by the two-path control system. The function of the pilot is to sense change in the controlled pressure and amplify it into a larger change in the loading pressure . Any changes in outlet pressure act quickly on both the actuator diaphragm and the loading pilot, thus providing the precise pressure control that is characteristic of a two-path system.

Features

  • High Capacity
  • High Accuracy
  • In-Line Maintenance
  • Pilot Supply Filter Standard
  • Excellent Low Flow Control
  • Tight Shutoff


Body Sizes and End Connection Styles

  • 2-inch (DN 50)
    • Cast Iron: NPT, 125FF, or 250 RF
    • Steel: NPT, SWE, 150 RF, or 300 RF


Pressure Registration

  • Internal


Maximum Inlet Pressure

  • 400 psig (27,6 bar) for higher inlet pressures, up to 1000 psig (69 bar)


Maximum Outlet Pressures

  • Operating: 100 psig (6,9 bar)


Outlet Pressure Ranges

  • 2-inches w.c. to 100 psig (5 mbar to 6,9 bar) in nine ranges


Temperature Capabilities

  • -20 to 180°F (-29 to 82°C)

Back to top


133 Series Pressure Reducing Regulators

 

 

The 133 Series direct-operated regulators are ideal for industrial and commercial applications supplying gas to furnaces, burners, and other appliances.  A balancing system enables the regulator to control gas pressure accurately for maximum combustion efficiency despite varying inlet pressures.



Features

  • Wide pressure range capability with single regulator
  • Types 133L, 133H and 133HP suitable for monitoring applications
  • Excellent shock characteristics and fast speed of response
  • Bubble-tight shutoff
  • Spring and diaphragm effects minimized
  • No seat-to-seat adjustment required
  • Easy access to trim parts
  • Reusable pressure seals
  • Resistance to piping stresses


Body Size and End Connection Styles

  • Cast Iron
    • 2-inch (DN 50) with NPT or 125A FF flanged end connections
  • Steel Body
    • 2-inch (DN 50) with NPT or 150 RF flanged end connections


Maximum Inlet Pressure

  • Operating:
    • 133L: 60 psig (4,1 bar)
    • 133H: 60 psig (4,1 bar)
  • Emergency:
    • 133L: 125 psig (8,6 bar)
    • 133H: 125 psig (8,6 bar)


Maximum Outlet (Casing) Pressure

  • 15 psig (1,03 bar)


Outlet Pressure Range

  • 2-inch w.c. to 10 psig (5 mbar to 0,69 bar) in 9 ranges


Temperature Capabilites

  • -20 to 150°F (-29 to 66°C)


Options

  • Restriction collar to reduce wide-open capacity to approximately 25,40, or 60 percent of standard wide-open capacity


Approximate Weights

  • 133H End Connection Style: NPT female  35 lbs (15,9 kg)
  • 133L End Connection Style: 125FF and 150RF 40 lbs (18,1 kg)

Back to top

133 Series Pressure Reducing Regulators

 

 

The 133 Series direct-operated regulators are ideal for industrial and commercial applications supplying gas to furnaces, burners, and other appliances.  A balancing system enables the regulator to control gas pressure accurately for maximum combustion efficiency despite varying inlet pressures.



Features

  • Wide pressure range capability with single regulator
  • Types 133L, 133H and 133HP suitable for monitoring applications
  • Excellent shock characteristics and fast speed of response
  • Bubble-tight shutoff
  • Spring and diaphragm effects minimized
  • No seat-to-seat adjustment required
  • Easy access to trim parts
  • Reusable pressure seals
  • Resistance to piping stresses


Body Size and End Connection Styles

  • Cast Iron
    • 2-inch (DN 50) with NPT or 125A FF flanged end connections
  • Steel Body
    • 2-inch (DN 50) with NPT or 150 RF flanged end connections


Maximum Inlet Pressure

  • Operating:
    • 133L: 60 psig (4,1 bar)
    • 133H: 60 psig (4,1 bar)
  • Emergency:
    • 133L: 125 psig (8,6 bar)
    • 133H: 125 psig (8,6 bar)


Maximum Outlet (Casing) Pressure

  • 15 psig (1,03 bar)


Outlet Pressure Range

  • 2-inch w.c. to 10 psig (5 mbar to 0,69 bar) in 9 ranges


Temperature Capabilites

  • -20 to 150°F (-29 to 66°C)


Options

  • Restriction collar to reduce wide-open capacity to approximately 25,40, or 60 percent of standard wide-open capacity


Approximate Weights

  • 133H End Connection Style: NPT female  35 lbs (15,9 kg)
  • 133L End Connection Style: 125FF and 150RF 40 lbs (18,1 kg)

Back to top


Type 310A Pressure Reducing Regulator



The Type 310A fuel pressure regulator is used for high-pressure applications which require fast response such as fuel gas supply to a gas turbine or other large volume applications. The Type 310A fuel pressure regulator includes one Type 32A pilot assembly mounted on the main valve for pressure reducing or wide-open monitoring applications.

The Type 310A fuel pressure regulator has accurate control, tight shutoff, high capacity, reduce relief requirements and fast speed of response.


In addition, minimum installation space is required for the Type 310A fuel pressure regulator.

Features

  • High Capacity
  • Tight Shutoff
  • Accurate Control
  • Minimum Installation Space Required


Body Sizes and End Connection Styles

  • 1-inch (DN 25) body with NPT end connection
  • 2, 3, 4 or 4 x 6-inch (DN 50, 80 100 or 100 x 200) bodies with 300 RF, 600 RF, or PN 25 or PN 40 end connection


Maximum Inlet Pressure

  • 1480 psig (102 bar)


Maximum Outlet (Casing) Pressure

  • 1480 psig (102 bar)


Outlet Pressure Ranges

  • 10 to 750 psig (0,69 to 52 bar) in five ranges


Pressure Registration

  • External


Temperature Capabilites

  • -20 to 300°F (-29 to 149°C)


Dimensions and Approximate Shipping Weights



Back to top

 

1098-EGR & 1098H-EGR Pressure Reducing Regulators

Type 1098-EGR and 1098H-EGR regulators provide accurate pressure control in a variety of applications: natural gas systems; fuel gas supply to industrial boilers, furnaces and mixers; and commercial or industrial businesses such as steel mils, asphalt plants, and shopping centers.  This regulator is used with a Type 6352, 6353, 6354 or 61 Series pilot.

The superior performance of this regulator is due to the amplifying effect of the pilot and the two-path control system.  Changes in outlet pressure act quickly on the actuator diaphragm to provide fast response to changes.  The pilot amplifies system changes, positioning the main valve for precise control.

Features

  • Labor-Saving Trim Maintenance
  • Ease of On-Site Maintenance
  • No Atmospheric Bleed
  • Noise Reduction Capability
  • Travel Indicator
  • NACE Configurations Available
  • Fixed Factor Billing
  • RegFlo" Compatible


Body Sizes and End Connection Styles

  • Cast Iron
    • 1 or 2-inch (DN 25 or 50) body sizes: NPT or ANSI Class 125FF or 250RF
    • 3, 4 or  6-inch (DN 80, 100 or 150) body sizes: ANSI Class 125FF or 250RF
  • Steel or Stainless Steel
    • 1 or 2-inch (DN 25 or 50) body sizes: NPT, BSP, ANSI Class 150RF, 300RF, 600RF, BWE, SWE, or P/N 16/25/40
    • 3, 4, 6, 8x6 or 12x6-inch (DN 80, 100, 150, 200x150 or 300x150) body sizes: ANSI Class 150RF, 300RF, 600RF, BWE, or P/N 16/25/40


Maximum Inlet Pressure

  • 400 psig (28 bar) or body rating limit whichever is lower


Maximum Outlet (Casing) Pressure

  • 1098: 115 psig (7,9 bar) depending upon actuator size
  • 1098H: 400 psig (27,6 bar)


Outlet Pressure Ranges

  • 2-inches w.c. to 300 psig (5 mbar to 20,7 bar) in 19 ranges


Pressure Registration

  • External


Temperature Capabilites

  • Neoprene or Nitrile: -20 to 150°F (-29 to 66°C)
  • Fluoroelastomer (FKM): 0 to 300°F (-18 to 149°C)


Shipping Weights

Body Size Inches (DN)

Approximate Shipping Weight, Pounds (kg)

1098 Size 30 Actuator

1098 Size 40 Actuator

1098 Size 70 Actuator

1 (25)

55 (25)

65 (29)

140 (64)

2 (50)

75 (34)

85 (39)

160 (73)

3 (80)

115 (52)

125 (57)

200 (91)

4 (100)

165 (75)

175 (79)

250 (113)

6 (150)

350 (159)

360 (163)

435 (197)

For larger sizes, please contact a Northeast Controls Sales Engineer.

Back to top

Type EZH Pressure Reducing Regulator

The Type EZH regulators are accurate pilot-operated, pressure balanced, soft seated regulators. They are designed for use in high pressure natural gas transmission/city gate stations, distribution systems, and power plant feeds. They provide smooth, reliable operation, tight shutoff and long life.

Available Configurations
Type EZH: Pilot-operated pressure reducing regulator for low to high outlet presure.
Type EZHOSX: Type EZH with an OS2 slam-shut device for overpressure or overpressure and underpressure protection.


Features

  • 1480 psig (102 bar) Inlet/Outlet Rating
  • Common Body Platform
  • Bubble Tight Shutoff
  • Absolutely No Atmospheric Bleed
  • Optional Slam-Shut Device
  • Full Usable Capacity
  • In-line Maintenance
  • Long Life in Severe Service Applications
  • Precise Pressure Control
  • High Turn Down Capability


Body Size and End Connection Styles

  • 1 or 2-inch (DN 25 or 50)
    • Main Valve Body Material: WCC Steel
    • End Connection Styles:  NPT or SWE, ANSI Class 150 RF, ANSI Class 300 RF, ANSI Class 600 RF or BWE
  • 3-inch (DN 80)
    • Main Valve Body Material: WCC Steel
    • End Connection Styles: ANSI Class 150 RF, ANSI Class 300 RF, ANSI Class 600 RF or BWE


Maximum Allowable Pressures

  • Inlet Pressure: 1480 psig (102 bar)
  • Outlet (Casing) Pressure: 1480 psig (102 bar)
  • Emergency Casing Pressure: 1480 psig (102 bar)
  • Operating Differential Pressure: 1480 psid (102 bar d)


Maximum Outlet Pressure

  • 435 to 1160 psig (30 to 80 bar)


Outlet Pressure Ranges

  • 7.3 to 1160 psig (0,5 to 80 bar) in ten ranges


Temperature Capabilites

  • -20° to 180°F (-29° to 82°C)


Approximate Weights

Weights, Pounds (kg)

Body Size, Inches (DN)

NPT

SWE

150RF

300RF

600RF

SCH 40

SCH 80

For OSX

1 (25)

77 (35)

77 (35)

79 (36)

83 (38)

87 (39)

77 (35)

77 (35)

Add 17 pounds (8 kg)

2 (50)

136 (62)

136 (62)

139 (63)

143 (65)

150 (68)

136 (62)

136 (62)

Add 30 pounds (14 kg)

3 (80)

390 (177)

390 (177)

394 (179)

397 (180)

410 (186)

390 (177)

390 (177)

Add 41 pounds (19 kg)

Back to top

Type EZR Pressure Reducing Regulator

The Type EZR pilot-operated, pressure reducing regulators are used for natural gas, air, or other non-corrosive gas applications and include a Type 112 restrictor and a 161EB Series pilot, 161AY Series pilot or a PRX Series pilot.  For applications that have high pressure drops, using a Type 161AYM, 161EBM, or 161EBHM monitor pilot will increase the accuracy of the regulator.

Type EZROSX with Slam-Shut Device
The optional slam-shut device can provide either overpressure or overpressure and underpressure protection by completely shutting off the flow of gas to the downstream system.The slam-shut has a mechanism box and a manometric device. The manometric device is a spring and diaphragm actuator. Its movement activates the detection stage of the mechanism box.The shutoff is a two stage process, the detection stage and the power stage.This separation between detection stage and power stage provides maximum precision, alleviating many false trips caused by environmental vibrations.

Features

  • Robust
  • Quiet Operation
  • Thoroughly Tested
  • Exceptional Design
  • Internally Actuated


Pressure Registration

  • External


Maximum Operating Inlet Pressure

  • 1050 psig (72,4 bar)


Body Sizes and End Connection Styles

  • Cast Iron
    • 2x1, 2, 3, 4, and 6-inch (DN 50x25, 50, 80, 100, and 150)
      • End Connection Styles(1)
        • NPT (2x1 and 2-inch only) (DN 50x25 and 50 only)
        • ANSI Class 125B FF
        • ANSI Class 250B RF
  • WCC Steel
    • 1, 1-1/4(2), 2x1, 2, 3, 4, 6x4, 8x4, 6, 8x6, 12 x 6-inch (DN 25, 32, 50x25, 50, 80, 100, 150x100, 200x100, 150, 200x150, and 300x150)
      • End Connection Styles(1)
        • NPT or SWE (1, 2x1 and 2-inch only) (DN 25, 50x25, and 50 only)
        • ANSI Class 150 RF
        • ANSI Class 300 RF
        • ANSI Class 600 RF or BWE
  • LCC Steel
    • 8-inch (DN 200)
      • End Connection Styles(1)
        • ANSI Class 150 RF
        • ANSI Class 300 RF
        • ANSI Class 600 RF

(1)Ratings and end connections for other than ANSI standard can usually be provided.
(2)Available in steel NPT only.

Pressure Registration

  • External


Options

  • Integral Slam-Shut Device
  • Prepiped Pilot Supply and Pilot Bleed
  • Travel Indicator
  • Inlet Strainer
  • Type 252 Pilot Supply Filter
  • Trim Package
  • Restricted Capacity Trim
  • Pilot Diaphragm for Pressure Loading
  • Quick Disconnect Union in Pilot Mounting


Approximate Weights



Back to top

 
Copyright © ICOM 2010. All rights reserved.