Type 99 Pressure Reducing Regulator

The Type 99 regulator typically provides fuel gas to boilers, furnaces, ovens, mixers, and large commercial or institutional installations.

The key to the operation of a Type 99 regulator is the yoked double-diaphragm pilot. Fast response and accuracy are made possible by the amplifying effect of the pressure-balanced pilot and by the two-path control system. The function of the pilot is to sense change in the controlled pressure and amplify it into a larger change in the loading pressure . Any changes in outlet pressure act quickly on both the actuator diaphragm and the loading pilot, thus providing the precise pressure control that is characteristic of a two-path system.

Features

  • High Capacity
  • High Accuracy
  • In-Line Maintenance
  • Pilot Supply Filter Standard
  • Excellent Low Flow Control
  • Tight Shutoff

Body Sizes and End Connection Styles

  • 2-inch (DN 50)
    • Cast Iron: NPT, 125FF, or 250 RF
    • Steel: NPT, SWE, 150 RF, or 300 RF

Pressure Registration

  • Internal

Maximum Inlet Pressure

  • 400 psig (27,6 bar) for higher inlet pressures, up to 1000 psig (69 bar)

Maximum Outlet Pressures

  • Operating: 100 psig (6,9 bar)

Outlet Pressure Ranges

  • 2-inches w.c. to 100 psig (5 mbar to 6,9 bar) in nine ranges

Temperature Capabilities

  • -20 to 180°F (-29 to 82°C)

Back to top

299H Pressure Series Regulator


The 299H Series regulators are pilot-operated pressure reducing regulators with the pilot integrally mounted to the actuator casing.  They are used in natural gas distrtibution systems, gas supply to industrial boilers, furnaces, ovens, mixers, and plant air service.  The Type 299HR has a token internal relief valve to relieve minor overpressure caused by thermal expansion.

This regulator has a pressure control accuracy of + 1% of absolute control pressure, making it an excellent choice for fixed factor billing or pressure factor measurement.

 

Features

  • +1% Accuracy for Fixed Factor Billing (PFM)
  • Wide Variety of Applications
  • Compact Size
  • Economical, Labor-Saving Installation
  • High-Capacity Pressure Control
  • No Atmospheric Bleed
  • Easy Registration Conversion

Body Sizes and End Connection Styles

  • Cast Iron
    • 1-1/4-inch (DN 32) body with NPT end connections
    • 1-1/2-inch (DN 40) body with NPT end connections
    • 2-inch (DN 50) body with NPT ends, ANSI Class 1251 FF and 250 RF flanged end connections
  • Ductile Iron
    • 1-1/2-inch (DN 40) body with NPT end connections
    • 2-inch (DN 50) body with NPT, ANSI Class 125 FF flanged, and  250 RF flanged, and PN 10 and 16 flanged end connections
  • Steel
    • 1-1/2-inch (DN 40) body with NPT end connections
    • 2-inch (DN 50) body with NPT, ANSI Class 150 RF flanged, and 300 RF flanged, or PN 16 flanged end connections

1This flange is available with a face-to-face dimension of 7.5-inches (191 mm) or 10-inches (254 mm).

Maximum Inlet Pressure

  • 175 psig (12,1 bar)

Maximum Outlet (Casing) Pressure

  • 66 psig (4,6 bar)

Outlet Pressure Ranges

  • 3-1/2-inches w.c. to 60 psig (9 mbar to 4,14 bar) in nine ranges

Minimum Differential Pressure for Full Stroke

  • 1.5 psig (0,10 bar)

Pressure Registration

  • Internal, External, or Dual Registration

Temperature Capabilites

  • -20 to 150°F (-29 to 66°C)

Approximate Shipping Weights

  • 21 pounds (9,5 kg)

Back to top

299HS Series Pressure Reducing Regulators with Slam-Shut Device

The 299HS Series with Type VSX-2 is used in applications where the gas supply must be shut off in the event of an accidental rise or drop in downstream pressure beyond a predetermined setpoint.  Pilot supply pressure also shuts off.  The Type 299HSR has a token internal relief valve to relieve minor overpressure caused by thermal expansion. 

The Type VSX-2 module on a 299HS Series is a fast-acting shutoff valve that provides over or underpressure protection by completely shutting off the flow of gas to the downstream system.  The shutoff module's actions are independent of the Type 299HS regulator and of variations in the inlet pressure.

Features

  • 1% Accuracy for Fixed Factor Billing (PFM)
  • Wide Variety of Applications
  • Compact Size
  • Economical, Labor Saving

Body Sizes and End Connection Styles

  • 1-1/2-inch (DN 40) NPT
  • 2-inch (DN 50) NPT; ANSI Class 125 and 250 flanged; or PN 10 flanged

Maximum Inlet Pressure

  • 175 psig (12,1 bar)

Maximum Outlet (Casing) Pressure

  • 66 psig (4,6 bar)

Minimum Differential Pressure for Full Stroke

  • 1.5 psig (0,10 bar)

Outlet Pressure Ranges

  • 3.5-inches w.c. to 16 psig (9 mbar to 1,10 bar) in seven ranges

Maximum Set Pressure for 299HS

  • 16 psig (1,10 bar)

Maximum Set Pressure for Slam-Shut Device

  • 23 psig (1,6 bar)

Slam-Shut Device Low-Pressure Set Pressure Range

  • 2-inches w.c. to 10.8 psig (6 mbar to 0,75 bar)in four ranges

Main Valve Pressure Registration

  • Internal, External, or Dual Registration

Slam-Shut Pressure Registration

  • Internal or External

Temperature Capabilites

  • -20 to 150°F (-29 to 66°C)

Approximate Shipping Weight

  • 21 pounds (9,5 kg)

Back to top


Type 627F Pressure Reducing Regulator


The Type 627F pilot-operated pressure reducing regulator provides superior performance when used in pressure factor measurement (fixed-factor billing) applications. The Type 627F includes a factory-installed Type 6351F pilot and has external registration that requires a downstream control line.

 

Features

  • Fixed Factor (PFM) Accuracy
  • Wide Range of Flow Capabilities
  • Tight Shutoff Capability
  • Easy to Maintain
  • Installation Adaptability
  • Tamper-Resistant

Body Size and End Connection Styles

  • Ductile Iron
    • 3/4-inch (DN 20) body size NPT end connection
    • 1 or 2-inch (DN 25 or 50) NPT
  • WCB Steel
    • 3/4-inch (DN 20) body size NPT, 300 RF or 600 Flanged
    • 1 or 2-inch (DN 25 or 50) NPT, 150 RF, 300 RF, 600 RF, or PN 16/25/40

Pressure Registration

  • External

Vent Connection

  • 1/4-inch NPT with removable screened vent assembly

Outlet Pressure Range

  • 5 to 100 psig (0,35 to 6,9 bar) in two ranges

Temperature Capabilites

  • -20 to 180°F (-29 to 82°C)


Approximate Weights

Configuration

Approximate Weight, Pounds (kg)

NPT body with ductile iron or steel casings

10 (4,5)

NPT body with aluminum casings

6.3 (2,9)

Flanged body with steel casings

18 (8,2)

Flanged body with ductile iron casings

14 (6,4)



Back to top

 

1098-EGR & 1098H-EGR Pressure Reducing Regulators


Type 1098-EGR and 1098H-EGR regulators provide accurate pressure control in a variety of applications: natural gas systems; fuel gas supply to industrial boilers, furnaces and mixers; and commercial or industrial businesses such as steel mils, asphalt plants, and shopping centers.  This regulator is used with a Type 6352, 6353, 6354 or 61 Series pilot.

The superior performance of this regulator is due to the amplifying effect of the pilot and the two-path control system.  Changes in outlet pressure act quickly on the actuator diaphragm to provide fast response to changes.  The pilot amplifies system changes, positioning the main valve for precise control.


Features

  • Labor-Saving Trim Maintenance
  • Ease of On-Site Maintenance
  • No Atmospheric Bleed
  • Noise Reduction Capability
  • Travel Indicator
  • NACE Configurations Available
  • Fixed Factor Billing
  • RegFlo" Compatible

Body Sizes and End Connection Styles

  • Cast Iron
    • 1 or 2-inch (DN 25 or 50) body sizes: NPT or ANSI Class 125FF or 250RF
    • 3, 4 or  6-inch (DN 80, 100 or 150) body sizes: ANSI Class 125FF or 250RF
  • Steel or Stainless Steel
    • 1 or 2-inch (DN 25 or 50) body sizes: NPT, BSP, ANSI Class 150RF, 300RF, 600RF, BWE, SWE, or P/N 16/25/40
    • 3, 4, 6, 8x6 or 12x6-inch (DN 80, 100, 150, 200x150 or 300x150) body sizes: ANSI Class 150RF, 300RF, 600RF, BWE, or P/N 16/25/40

Maximum Inlet Pressure

  • 400 psig (28 bar) or body rating limit whichever is lower

Maximum Outlet (Casing) Pressure

  • 1098: 115 psig (7,9 bar) depending upon actuator size
  • 1098H: 400 psig (27,6 bar)

Outlet Pressure Ranges

  • 2-inches w.c. to 300 psig (5 mbar to 20,7 bar) in 19 ranges

Pressure Registration

  • External

Temperature Capabilites

  • Neoprene or Nitrile: -20 to 150°F (-29 to 66°C)
  • Fluoroelastomer (FKM): 0 to 300°F (-18 to 149°C)


Shipping Weights

Body Size Inches (DN)

Approximate Shipping Weight, Pounds (kg)

1098 Size 30 Actuator

1098 Size 40 Actuator

1098 Size 70 Actuator

1098H Size 30 Actuator

1 (25)

55 (25)

65 (29)

140 (64)

80 (36)

2 (50)

75 (34)

85 (39)

160 (73)

100 (45)

3 (80)

115 (52)

125 (57)

200 (91)

140 (64)

4 (100)

165 (75)

175 (79)

250 (113)

190 (86)

6 (150)

350 (159)

360 (163)

435 (197)

375 (170)

For larger sizes, please contact a Northeast Controls Sales Engineer.


Back to top

Type HSR Direct-Operated, Spring-Loaded Pressure Regulators

The Type HSR direct-operated, spring-loaded pressure regulators provide economical pressure reducing control in a variety of residential, commercial, and industrial applications. The Type HSR pressure regulators can be used with natural, manufactured, or liquefied petroleum gases. In addition, the Type HSR pressure regulators have internal relief across the diaphragm to help minimize overpressure. Any outlet pressure above the start-to-discharge point of the nonadjustable relief valve spring moves the diaphragm off the relief valve seat, allowing excess pressure to bleed out through the screened spring case vent.

The Type HSR pressure regulators meet ANSI B109.4 / CGA 6.18.

Features

  • Angle Bodies
  • Globe Bodies
  • High Capacity
  • Compact Design
  • High Capacity Internal Relief
  • Meets or Exceeds ANSI B109.4 / CGA 6.18 Requirements
  • Fixed Factor / PFM Accuracy

Body Size and End Connection Styles

  • 3/4 x 3/4-inch (DN 20 x 20)
  • 3/4 x 1-inch (DN 20 x 25)
  • 1 x 1-inch (DN 25 x 25) NPT
  • All sizes available in Globe or Angle Body

Allowable Inlet Pressure

  • Emergency: 150 psig (10,3 bar)
  • Maximum Operating Pressure: 125 psig (8,6 bar)

Allowable Outlet Pressure

  • Emergency (Casing): 25 psig (1,7 bar)
  • Maximum Operating Pressure to Avoid Internal Parts Damage: 3 psi (0,21 bar) differential above outlet pressure setting

Outlet Pressure Ranges

  • 6-inches w.c. to 2.2 psig (15 mbar to 0,15 bar) in 5 ranges

Temperature Capabilites

  • -20° to 160°F (-29° to 71°C)

Pressure Registration

  • Internal

Back to top


S200 Series Pressure Reducing Regulators

The quick-reacting S200 Series pressure reducing service regulator is typically used in an industrial or commercial installation to minimize the shock effect of sudden downstream load changes that might otherwise activate safety shutoff equipment. In such an installation, where gas consumption varies from almost nothing to several thousand standard cubic feet per hour (scfh) (or normal cubic meters per hour (m3/h(n)), snap-acting solenoid valves can cause sudden load changes. The resulting shock pressures and regulator instability can cause safety equipment to shut the installation down. But with an S200 Series regulator, transmission of shock loads to downstream equipment is reduced, thereby helping maintain downstream pressures within desired limits.

The S200 Series regulators are available in several different configurations to meet the demands of varying services and overpressure protection requirements. Each configuration is made up of different construction features. The following section describes the available construction features.

Available Configurations
The S200 Series regulators are available in several different configurations to meet the demands of varying services and overpressure protection requirements. Each configuration is made up of different construction features. The following section describes the available construction features.
S201 Series

  • S201: Basic construction without internal relief for 2 to 30-inches w.c. (5 to 75 mbar) outlet pressures
  • S201H: S201 with a heavy diaphragm plate for 1 to 5 psig (0,069 to 0,34 bar) outlet pressures
  • S201K: S201 with a heavy diaphragm plate for 2 to 10 psig (0,14 to 0,69 bar) outlet pressures
  • S201P: S201 with downstream control line connection and O-ring stem seal for external pressure registration
  • S201PK: Combination of S201K and S201P

S202 Series

  • S202: S201 basic construction for 2 to 30-inches w.c. (5 to 75 mbar) outlet pressures with internal relief
  • S202H: S201 with a heavy diaphragm plate for 1 to 5 psig (0,069 to 0,34 bar) outlet pressures with internal relief
  • S202P: S201 with downstream control line connection, O-ring stem seal for external pressure registration, and internal relief

S203 Series

  • S203, S203H, S203P
    • S201, S201H, and S201P constructions with "True" monitor regulator to provide overpressure protection. Available in cast iron body only.

S204 and S206 Series

  • S204 and S204H
    • S201 and S201H constructions with a low outlet pressure shutoff. Available in cast iron body only.
  • S206 and S206H
    • S202 and S202H constructions with a low outlet pressure shutoff. Available in cast iron body only.

S208 and S209 Series

  • S208, S208H, S208P, S208K, S208PK
    • S201, S201H, S201P, S201K, and S201PK constructions with a Type VSX-2 slam-shut device to provide overpressure (OPSO) or over and underpressure (UPSO) protection. Available in ductile iron body only.
  • S209, S209H, S209P
    • S202, S202H, and S202P constructions with a Type VSX-2 slam-shut device to provide overpressure (OPSO) or over and underpressure (UPSO) protection. Available in Ductile iron body only.


Features

  • Fixed Factory Billing / PFM Applications - The S200 Series can maintain outlet pressure accuracy for applications that require downstream pressure to be held within ± 1% absolute pressure.
  • Internal Relief Valve - The Types S202, S202H, S202P, S206, S206H, and S209 have internal relief across the diaphragm to help minimize overpressure.
  • Wide Outlet Pressure Range - The S200 Series has a wide range of outlet pressure settings from 2-inches w.c. to 10 psig (5 mbar to 0,69 bar).
  • Retrofittable - The S200 Series and the 299H Series use the same body and orifices. As a result, the S200 Series can easily be upgraded to a 299H Series without removing the regulator body from the pipeline.
  • Multiple Orifice Sizes - Several choices of orifice sizes to accommodate wide range of flow and inlet pressures.
  • Easy Inspection - The S200 Series uses a rugged tow-bolt actuator to body connection, which allows the easy and reliable access to the orifice and seat disk for inspection.
  • Integral Slam-Shut Device - The S200 Series can be configured with a Type VSX-2 integral slam-shut device to provide Overpressure Shutoff (OPSO) or Over (OPSO) and Underpressure Shutoff (UPSO).
  • "True" Monitor - The S200 Series can be configured with an intergral monitor, which functions independently from the main regulator to limit downstream pressure.


Maximum Emergency Inlet Pressure (Body Rating)

  • 175 psig (12 bar), except 125 psig (8,6 bar) for Type S201D regulator with optional Type S251 loading regulator. See the S200 Series Product Bulletin for Maximum Operating Inlet Pressure for specific type numbers.

Maximum Outlet Pressure (Casing)

  • 15 psig (1,0 bar)

Outlet Pressure Range

  • 2-inches w.c. to 10 psig (5 mbar to 0,69 bar).

Pressure Registration

  • Internal or External

Temperature Capabilites

  • -20 to 180°F (-29 to 82°C)

Back to top

S208 and S209 Series Pressure Reducing Regulators with Slam-Shut Device


The quick-reacting Types S208 and S209 pressure reducing regulator are typically used in an industrial or commercial installation to minimize the shock effect of sudden downstream load changes. The S208/S209 Series regulators have the same basic construction as the S200 Series regulators. The Type S209 regulators have limited capacity internal relief across the diaphragm to help minimize overpressure. Both the Type S208 and S209 are available in high pressure versions, Type S208H and S209H.


Features

  • Installation Adaptability
  • Excellent Shock Characteristics and High Speed or Response
  • Control Accuracy
  • Easy Maintenance

Body Size and End Connection Styles

  • 1-1/4, 1-1/2, or 1-1/2 x 2-inch body size NPT screwed end connection
  • 2-inch body size NPT screwed, 125A RF, or 250A RF flanged end connections

Maximum Inlet Pressure

  • 125 psig (8,6 bar)

Maximum Outlet (Casing) Pressure

  • 15 psig (1,0 bar)

Outlet Pressure Ranges

  • 3.5-inches w.c. to 5 psig (9 to 345 mbar) in 13 ranges

Pressure Registration

  • Internal and External

Temperature Capabilites

  • Type S208/S209: -20 to 180°F (-29 to 82°C)
  • VSX Module: -20 to 140°F (-29 to 60°C)

Back to top

S300 Series Pressure Reducing Regulators



The S300 Series direct-operated, spring-loaded regulators are used for pressure reducing control in a variety of commercial, institutional, and industrial applications. All regulators in this series are used with natural, manufactured, or liquefied petroleum gases.




Features

  • Fixed Factor (PFM) Accuracy
  • Installation Adaptability
  • Easy Maintenance
  • Accurate Control
  • Excellent Shock Characteristics
  • High Speed of Response

Body Size and End Connection Styles

  • S303, S303H, and S303P
    • 1-1/4 or 1-1/2-inch body size NPT screwed or 125 FF flanged end connections
    • 2-inch body size NPT screwed end connection
  • All other Types
    • 1-1/4, 1-1/2, or 2-inch body size NPT screwed or 125 FF flanged

Maximum Inlet Pressures

  • 150 psig (10,3 bar)

Maximum Outlet (Casing) Pressure

  • 15 psig (1,0 bar)

Outlet Pressure Range

  • 3-1/2-inches w.c. to 8 psig (0,87 to 0,55 bar) in seven ranges

Temperature Capabilites

  • -20 to 160°F (-29 to 71°C)

Back to top

 